Digital Airflow Signal Processor
|
|
|
|
|
|
MicroTransEQ Airflow Signal Processor
|
|
|
|
|
|
The MicroTransEQ flow transducer utilizes a 24 bit A/D converter for
signal processing and can produce accuracies of ±0.1% of reading. The ultra low
0.03"w.c. differential pressure (693 fpm at standard air density conditions) full
scale operating range and the auto zeroing function provides accurate air flow measurement
down to 100 fpm making this product ideal for outdoor air flow measurement applications
and for use on projects seeking to obtain credit for IEQ Credit 1: Outdoor Air Delivery
Monitoring under the LEED® Green Building Rating System. The MicroTransEQ
also accepts a temperature input signal for air density compensation for standard
or actual airflow calculations. For easy use on fan inlet applications with piezometer
ring systems, the MicroTransEQ incorporates a special piezometer ring
flow algorithm with easy flow coefficient entry through display menus. A 4-point
flow correction and K-factor field menu are included to reduce time and save money
spent on balancing. Device monitoring and configuration can also be performed by
a building management system through either a LonWorks®, BACnet-MS/TP®
Master or Modbus communication network.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|