Differential Pressure Transducers
|
|
|
|
|
|
DPT-4001 Loop Powered Differential Pressure Transducer
|
|
|
|
|
|
The DPT-4001 differential pressure transducer sensor operates on the capacitance
principal and is capable of sensing ultra low differential pressures. In the capacitance
cell, a very lightweight, responsive diaphragm deflects a small amount when pressure
is applied. This deflection results in a change in capacitance, which is then detected
and processed electronically into 4-20 mA output signal linear to the differential
pressure.
|
|
|
|
|
|
|
|
|
|
|
DPT-4003 Differential Pressure Transducer
|
|
|
|
|
|
The DPT-4003 differential pressure transducer sensor operates on the capacitance
principal and is capable of sensing ultra low differential pressures. In the capacitance
cell, a very lightweight, responsive diaphragm deflects a small amount when pressure
is applied. This deflection results in a change in capacitance, which is then detected
and processed electronically into a 0-5 or 0-10 VDC output signal linear to the
differential pressure.
|
|
|
|
|
|
|
|
|
|
|
DPT & DPIT-4005 Series Differential Pressure Transducers
|
|
|
|
|
|
DPT & DPIT-4005 Series are analog four wire differential pressure transducers
with a scaling multiplier and output filter complete in a single package. The 4-20
mA, 0-5 VDC, or 0-10 VDC selectable output of the transducers is linear to velocity
pressure. Each transducer is factory spanned and calibrated to meet the design requirement
of the application. Optional features include local indication of the measured differential
pressure on an independent front panel mounted magnehelic pressure gauge (Model
DPIT-4005-M).
|
|
|
|
|
|
|
|
|
|
|
MicroTransEQ Airflow Signal Processor
|
|
|
|
|
|
The MicroTransEQ flow transducer utilizes a 24 bit A/D converter for
signal processing and can produce accuracies of ±0.1% of reading. The ultra low
0.03"w.c. differential pressure (693 fpm at standard air density conditions) full
scale operating range and the auto zeroing function provides accurate air flow measurement
down to 100 fpm making this product ideal for outdoor air flow measurement applications
and for use on projects seeking to obtain credit for IEQ Credit 1: Outdoor Air Delivery
Monitoring under the LEED® Green Building Rating System. The MicroTransEQ
also accepts a temperature input signal for air density compensation for standard
or actual airflow calculations. For easy use on fan inlet applications with piezometer
ring systems, the MicroTransEQ incorporates a special piezometer ring
flow algorithm with easy flow coefficient entry through display menus. A 4-point
flow correction and K-factor field menu are included to reduce time and save money
spent on balancing. Device monitoring and configuration can also be performed by
a building management system through either a LonWorks®, BACnet-MS/TP®
Master or Modbus communication network.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ABOUT
Theory of Operation
|
|
|
|
|
|
ABOUT
Installation Guidelines
|
|
|
|
|
|
|
|
ABOUT
Airflow Measurement Accuracy
|
|
|
|
|
|
|
|
|
|
|
|
|